Mitsubishi — 3.7 Numbering and Functions of Counters [C]

3 Functions of Devices in DVP-PM Input pulse Pulse X6 U A PV of C212 Dir C212 X7 Input pulse D B M1213/M1212 Counting mode selection C212 reset signal M1215=1, X13- z Counting mode of C216 is selected by M1216/M1217. Input signal of C216 is controlled by X10/X11. Reset signal of C216 is enabled by M1219 and triggered by X0. Input pulse Pulse X10 U A PV of C216 C216 Input pulse Dir D X11 B Counting mode selection M1217/M1216 C216 reset signal M1219=1, X0 z Counting mode of C220 is selected by M1220/M1221. Input signal of C220 is controlled by X12/X13. Reset signal of C220 is enabled by M1223 and triggered by X1.

Input pulse Pulse U A PV of C220 Dir C220 X13 Input pulse D B M1221/M1220 Counting mode selection C220 reset signal M1223=1, X1 4. SV can be K value (decimal) or D register (Special data register D1000~D2999 is not included). SV can be a positive or negative value. If a D register is specified as SV, it will occupy 2 consecutive data registers. 5. PV in the general purpose counter will be cleared when power of DVP-PM is OFF. If the counter is a latched (accumulative) type, PV and the contact status will be retained, and PLC will resume counting after power is ON again. 6. When PV reaches up to 2,147,483,647, the next PV will turn to -2,147,483,648.

When PV reaches down to -2,147,483,648, the next PV will turn to 2,147,483,647 DVP-PM Application Manual 3-15