Mitsubishi — 3.11 Functions of Special Auxiliary Relays and Special Registers

3 Functions of Devices in DVP-PM Function Group: Enabling force-ON/OFF of input point X Number: M1304 Explanations: When M1304 = ON, the peripheral devices, e.g. PMSoft, can force input ponts X0~X17 to be ON/OFF. However, the LED will not respond to the ON/OFF state in this case. Function Group: ID of right-side modules Number: D1320 ~ D1327 Explanations: 1. When I/O modules are connected, the ID of each I/O module will be stored in D1320~D1327 in connection order. 2. ID of Special I/O modules for DVP-PM: Function Group: Interruption Number: D1400, D1401 Explanations: 1. To enable the interrupts below, please set ON the corrensponding bits of D1400. Note:

X0*~X7* are applicable only for DVP-10PM 2. If timer interruptipon is enabled, please enter the interrupt interval in D1401 3. There 2 types of interrupts including external interrupt and timer interrupt: „ External interrupt: When the external terminal is triggered by the rising/falling edge of an input signal, the current executing program will be interrupted and the interrupt subroutine will be executed immediately DVP-PM Application Manual 3-43 Module Name Module ID (hex) Module Name Module ID (hex) DVP04AD-H2 H’6400 DVP01PU-H2 H’6110 DVP04DA-H2 H’6401 DVP04PT-H2 H’6402 DVP04TC-H2 H’6403 DVP06XA-H2 H’6604 DVPPM H’6260 DVP01HC-H2 H’6120 bit# Interruption No.

0 Timer interrupt I0 1 External interrupt Start0 / X0* I1 2 External interrupt Stop0 / X1* I2 3 External interrupt Start1 / X2* I3 4 External interrupt Stop1 / X3* I4 5 External interrupt X4* I5 6 External interrupt X5* I6 7 External interrupt X6* I7 8 External interrupt X7* I8