Mitsubishi — 3.11 Functions of Special Auxiliary Relays and Special Registers

3 Functions of Devices in DVP-PM For input terminals below, setting the corresponding bit# to be ON will define the input terminal as NO contact; setting the corresponding bit# to be OFF will define the input terminal as NC contact. 20PM : 10PM : Function Group: Reading Input terminal status 2 (for Z-axis) Number: D1805 Explanations: When there is signal input at the input terminal, the corresponding bit# = ON. If not, the corresponding bit# = OFF 20PM : 10PM : Function Group: Filter coefficient Number: D1806 Explanations: 1. The low byte of D1806 sets the filter coefficient of the input terminals START, STOP, DOG, LSN, LSP and PG 2.

The high byte of D1806 sets the filter coefficient of the inut terminal MPG0/MPG1. 3. Filter coefficient 4 N 2 85000 + = (KHz), N = 1~19; the conversion results are as below: DVP-PM Application Manual 3-49 bit# Polarity of input terminal 0 PG2 1 MPGB1 2 MPGA1 3 LSN2 4 LSP2 5 DOG2 bit# Polarity of input terminal 0 X3(DOG3) 1 MPGB1 2 MPGA1 3 X2(DOG2) 4 X1(DOG1) 5 X0(DOG0) bit# Input terminal status 0 PG2 1 MPGB1 2 MPGA1 3 LSN2 4 LSP2 5 DOG2 bit# Input terminal status 0 X3(DOG3) 1 MPGB1 2 MPGA1 3 X2(DOG2) 4 X1(DOG1) 5 X0(DOG0) N kHz N kHz 1 2656.25 11 2.593994 2 1328.125 12 1.296997 3 664.0625 13 0.648499 4 332.0313 14 0.324249