3 Functions of Devices in DVP-PM 4. When D1806 = 0, the filter function on external terminals will be disabled. 5. For example, if D1806 is set as H0A0A, the filter coefficient on input terminals START, STOP, DOG, LSN, LSP and PG and MPG0/1 will be: 5.187988 2 85000 4 10 = + (KHz), i.e. input frequency higher than 5.187988KHz will be filtered out. Function Group: Error Status of O100 Number: M1953, D1802, D1803 Explanations: 1. When errors occur in O100 program, O100 error flag M1953 will be ON, the error code will be stored in D1802, and error step will be stored in D1803. 2. See the table of error messages in Appendix of Chapter 14. Function Group: Parameter Setting of X-Y-Z-A Axis Number:
D1816, D1896, D1976, D2056 Explanations: Parameter setting of X axis: D1816, Y axis: D1896, Z axis: D1976 and A axis: D2056. See the tables below: Note: PWM mode is only applicable for DVP-10PM Note *1:
DVP-PM Application Manual 3-50 5 166.0156 15 0.162125 6 83.00781 16 0.081062 7 41.50391 17 0.040531 8 20.75195 18 0.020266 9 10.37598 19 0.010133 10 5.187988 bit# X-Y-Z axis parameter setting bit# X-Y-Z axis parameter setting 0 Unit (*1) 8 Zero return direction (*4) 1 9 Zero return mode (*4) 2 Multiplication of position data (*2) 10 DOG signal rising/falling edge triggered (*4) 3 11 Reverse the displacement direction in same pulse output polarity (*4) 4 Pulse type (*3) 12 Relative/absolute positioning (*4) 5 13 DOG signal rising/falling edge triggered (for single/ 2 speed positioning interruption mode) (*4) 6* PWM mode (*4) 14 Curve selection (*4) 7 15