SC523 Chassis Manual Chapter 6: Rack Installation 6-4 Rack Mounting Instructions This section provides information on installing the SC523 chassis into a rack unit with the rails provided. There are a variety of rack units on the market, which may mean the assembly procedure will differ slightly. You should also refer to the instal- lation instructions that came with the rack unit you are using. B 1 A NOTE: The rails will fit a rack between 29" and 35.25" deep. 1 C The chassis package includes two rail assemblies in the rack mounting kit. Each assembly consists of two sections:
an inner fixed chassis rail that secures directly to the server chassis and an outer rack rail that secures directly to the rack itself. Identifying the Sections of the Rails Separating the Inner and Outer Rails Figure 6-1. Inner and Outer Rails 1. Pull the inner rail (A) from the outer rail (B) as far as possible. Rail Brackets 2. Depress the locking tab (C) to pull the inner rail completely out and separate it from the outer rail. The chassis package includes four rail brackets and two chassis mounts. The rail brackets have long ovals used to adjust the length of the rails when mounting. The chassis mounts (both short) have one square hole. 3. Repeat steps 1 and 2 for the other rail.
Inner Rail Inner Rail Figure 6-2. Rail Installation Installing the Inner Rail 1. Align the inner rail with the side of the chassis. 2. Secure the inner rail to the chassis using six M5 flat head screws. 3. Repeat steps 1 and 2 for the remaining inner rail. Warning: do not pick up the server by the front handles. They are designed to pull the system from a rack only. 6-4 6-5