2. Internal speed The speed is selected through the digital input signal control: 5.3.3 Soft Start The soft start function is a speed command that converts a step speed command to a smoother constant acceleration/deceleration. You can set the acceleration time and deceleration time, and use this function when you want to achieve smooth speed control during speed control.

96 SD700 Series Servo Technical Manual Function Parameter Range Default Unit Communication address When enabled code Pn304 Pn305 Pn306 Internal speed 1 0~10000 100 rpm 0x0304 Immediately Internal speed 2 0~10000 200 rpm 0x0305 Immediately Internal speed 3 0~10000 300 rpm 0x0306 Immediately When operating in the internal speed mode, the servo unit provides 3 internal speed commands and selects A and B through the switching value internal speed command. When the switching value internal speed command selects A and B at OFF state, the internal speed is default as 0.

Switching value input signal Direction of speed instruction Speed instruction /SPD-D /SPD-A /SPD-B OFF OFF OFF Positive 0 OFF ON Internal speed 1(Pn304) ON ON Internal speed 2(Pn305) ON OFF Internal speed 3(Pn306) ON OFF OFF Negative 0 OFF ON Internal speed 1(Pn304) ON ON Internal speed 2(Pn305) ON OFF Internal speed 3(Pn306) Function Parameter Range Default Unit Communication address When enabled code Pn310 Speed command trapezoidal acceleration time 0~ 10000 0 ms 0x0310 Immediately Acceleration time of the set speed is from 0r/min to the max speed (corresponding to the motor model).

When the given speed is more or less than the max speed, the actual acceleration time is calculated in proportion. Pn311 Speed command 0~ 0 ms 0x0311 Immediately