Torque / % Defaults Maximum output voltage +10V - Voltage / V 5.4.3 Adjustment of Command Offset When using torque control, even if the command is 0V, the servo motor may rotate at a slight speed. This is because there is a slight deviation in the Commands inside the servo unit. This slight deviation is called “offset”. There are two methods of automatic adjustment and manual adjustment of offset adjustment. Automatic adjustment is automatically adjusting the command offset (Fn100) and manual adjustment is manually adjusting using command offset (Fn102). For details, see “Auxiliary Functions”. ! 1.

For automatic adjustment, be sure to adjust the command bias amount in the state of servo OFF and the upper computer (PLC, knob, etc.) giving 0v voltage command. 2. When adjusting manually, observe the operation of the motor while adjusting in the state of servo ON. 3. If the factory setting is restored, the offset adjustment value will not be initialized. Cautions 103 SD700 Series Servo Technical Manual 350% mum output voltage-10V 200% 100% 10 - 3 - 1 Maximu 1 3 10 Setting range 1V~10V corresponding to rated -350% Input voltage range 0V~± 10V Torque Offset T-REF Voltage Torque After offset adjustment T-REF voltage