VEICHI — SD700 User Manual 20230516

Robust control function is valid in position control or speed control and invalid in torque control. When robust control is valid, some of the control functions of below table would be restrained. Which parameters become invalid when robust control function are valid. When we set robust control function valid in factory default, the Pn100, Pn101, Pn102, Pn103, Pn105, Pn106, Pn107, Pn140, Pn110, Pn170 are invalid. 6.2.2 Operating Procedure Robust control function could be set via the auxiliary function Fn301 on panel operator and more details on “Auxiliary function”, or we could set relevant parameters via “parameters setting”.

! Before operating the robust control function, please confirm the setting below, if not, it will display /NO- OP in operation: 1. Robust control function is valid (Pn175=1). 2. No motor debugging function is invalid (Pn730=0). Cautions 6.2.3 Additional Notes In robust control, due to the increase of the tuning value, the system may cause resonance noise. It 122 SD700 Series Servo Technical Manual Pn175 Robust control selection 0x00~ 0x01 1 - 0x0175 After restart Set the robust control function switch:

0-invalid 1-valid Pn177 Robust control tuning value 10~80 40.0 Hz 0x0177 Immediately Set a greater robust control gain tuning value, systematic response gets faster, but system overshoot and excessive noise may occur. Pn178 The minimum value of robust control 0~500 0 % 0x0178 Immediately Set a greater load ratio of robust control, systematic response gets faster, but the systematic excessive noise may occur, and we could increase this value in order to decrease the over-adjustment and overshoot when torque is excessive.

Function name Operation Executable conditions and notes Vibration detection value initialization (Fn105) Yes Robust control is invalid in operation, and it turns to be valid when the operation is over. Bandwidth setting (Fn303) No EasyFFT (Fn401) Yes Robust control is invalid in operation, and it turns to be valid when the operation is over. Gain shift No Inertia recognition Yes Robust control is invalid in operation, and it turns to be valid when the operation is over. Mechanical analysis Yes Robust control is invalid in operation, and it turns to be valid when the operation is over.