“Auto switching gain” is only valid in position control. The switching conditions are performed by the following settings: Switching logic For example, in the automatic switching gain mode conditioned on the completion of the positioning signal (/COIN), it is assumed that the position loop gain Pn103 is switched to the second position loop gain Pn107. The /COIN signal of the switching condition is ON, and after waiting for the waiting time Pn114 from the time when the switching condition has been met, the gain is linearly changed from Pn103 to Pn107 during the switching time Pn112.
Switching time Waiting time /COIN Switching condition is met 136 SD700 Series Servo Technical Manual Function Communication When Parameter Range Default Unit code address enabled Pn111 Position control gain automatic switching condition 0x00~ 0x05 0 - 0x0111 Immediately Set the conditions for automatic gain switching: 0-Position completion signal ON. 1-Position completion signal OFF. 2-positioning proximity signal ON. 3-positioning proximity signal OFF. 4-position command filtered to 0 and pulse input OFF. 5-position command pulse input ON. If the condition is met, switch to the 2nd gain, otherwise switch to the 1st gain.
Switching Switching Switching Switching Parameter conditions gain waiting time time Condition A is met The first gain → Second gain Waiting time 1 Pn114 Switching time 1 Pn112 Pn111 setting corresponding Condition A isn’t met The second gain → First gain Waiting time 2 Pn115 Switching time 2 Pn113 condition A Position loop gain P n103 Pn114 Pn112 The second position loop gain Pn107 ON OFF