7.2.2 Operating Procedure Long press DATA/SHIFT Auxiliary function display Old alarm Any interface MODE/SET alarm Alarm record Long press DATA/SHIFT Low alarm recording Latest UP: previous code DOWN: next code Short press DATA/SHIFT time Old alarm Auxiliary Long press DATA/SHIFT Short press DATA/SHIFT Short press DATA/SHIFT Short press DATA/SHIFT Alarm recording Alarm recording time median digit function time high digit 7.3 Clear Alarm Record (Fn001) 7.3.1 Summary The alarm record of the servo unit can only be cleared by clearing the alarm record (Fn001) function. Alarm recording cannot be cleared by resetting the alarm or switching off the main circuit power of the servo unit.
7.3.2 Operating Procedure DATA/SHIFT Long press Auxiliary function Any interface MODE/SET Auxiliary function UP Clear alarm record DATA/SHIFT Long press Alarm clear MODE/SET confirmation Clear Flash 2s 7.4 Software Reset (Fn002) 7.4.1 Summary The function enables resetting the servo unit internally from software. It is used when it needs to re- power on or reset the alarm after changing the parameter setting. Parameter setting could also be enabled without re-power on. ! 1. This function must be operated in the state of servo OFF. 2. This function has nothing to do with the upper unit, and can reset the servo unit. Handling as when power is turned on.
The servo unit will output the ALM signal, and other output signals may be changed forcibly. Cautions 143 SD700 Series Servo Technical Manual