times of movements. Same as JOG operation (Fn005), do not connect to the host device during setting while using this function. It could confirm the operation of the servo motor and perform simple positioning operations. ! 1. Program JOG runs as position control, gear ratio and position command filtering are valid, but it is not possible to input pulse command to the servo The pulse command cannot be input to the servo unit. 2. Overtravel prevention function is effective.
Cautions 7.7.2 Operating Procedure preparation Any interface MODE/SET UP Long press DATA/SHIFT Program JOG Auxiliary Program JOG MODE/SET Enabled ON UP/DOWN in the setting direction function End of operation MODE/SET Long press DATA/SHIFT preparation JOG working process Program JOG Long press DATA/SHIFT 7.8 Automatic Adjustment of Command Offset (Fn100) 7.8.1 Overview The automatic adjustment command offset is a method of automatically adjusting the command voltage after measuring the offset. The measured offset will be stored in the servo unit. ! 1. Servo is in OFF state. 2.
The bias adjustment is out of range or the voltage command is input during the bias adjustment, the adjustment may fail. Cautions 7.8.2 Operating Procedure Turn off the servo drive and input the 0V command voltage from the host device or external circuit. 146 SD700 Series Servo Technical Manual