230 SD700 Series Servo Technical Manual A/B pulse phase sequence selection. 0- Don’t negate the pulse output: When forward run, B is ahead of A. 1- Negate the pulse output: When forward run, A is ahead of B. Pn080 Local communication address 0x00~ 0x7F 1 - 0x0080 After restart During RS-485 communication, this parameter is the 485 communication station number, and during CANopen communication, this parameter is the CANopen slave station number.
Pn081 485 communication baud rate selection 0~4 1 - 0x0081 After restart 0bps-9600bps 1bps-19200bps 2bps-38400bps 3bps-57600bps 4bps- 115200bps Pn082 485 communication verification method 0~5 1 - 0x0082 After restart 0-No check (N,8,1) 1-Even check (E,8,1) 2-Odd check (O,8,1) 3-No check (N,8,2) 4-Even Check (E,8,2) 5-Odd Check (O,8,2) Pn083 CANopen communication baud rate selection 0~6 4 - 0x0083 After restart 0: 20kbps 1: 50kbps 2: 100kbps 3: 125kbps 4: 250kbps 5: 500kbps 6: 1000kbps Communication data storage EEPROM 0x0~ 0xFFF 0x1 - 0x0085 Immediately Bit0: 0: Store data to EEPROM. 1: Do not store data to EEPROM. Bit1: 0:
During power on and start, the value Bit0 of Pn085 is forced to be 1. 1: During power on and start, the value Bit0 of Pn085 is not forced to be 1. Panel keypad operation setting: 00: Modify the data, power off and store it in EEPROM. After servo restart, Pn085 changes to 01. After connecting the upper computer, 00 is displayed. Disconnect the upper computer and power on again. The panel displays Pn085 as 01 again (Data is not stored in EEPROM when power on, but is stored in EEPROM when power off).
Pn085 Communication address mapping function selection 0~1 0 - 0x0086 Immediately Pn086 0:Close 1:On Mapping source address 1 0x0000~ 0xFFFF 0x110 - 0x0087 Immediately Pn087 Mapping destination address 1 0x0000~ 0xFFFF 0x410 - 0x0088 Immediately Pn088 Mapping source address 2 0x0000~ 0xFFFF 0x201 - 0x0089 Immediately Pn089 Mapping destination address 2 0x0000~ 0xFFFF 0x304 - 0x008A Immediately Pn08A Encoder over temperature alarm threshold (℃) 0~255 80 ℃ 0x008B After restart Pn08B The over temperature alarm value of Nikon encoder is fixed at 90℃. and Pn08b has no effect on the change of over temperature alarm value of Nikon encoder.
There is no encoder over temperature alarm for Tamagawa encoder below 80 (including) flange. For encoder that cannot detect over temperature alarm, pn08b will be automatically written as 0 in the program; The encoder over temperature alarm will