242 SD700 Series Servo Technical Manual Pn269 Position deviation warning threshold when the Servo is ON 10~100 100 % 0x0269 Immediately This parameter is used to set the warning threshold for excessive position deviation at the servo ON moment. When the servo is turned ON and the position deviation is greater than the product of “Excessive position deviation warning threshold at servo ON” and the parameter, the warning will be generated when the servo is ON. Pn270 Speed limit value when the Servo is ON 0~10000 10000 rpm 0x0270 Immediately If the servo is turned ON with the position deviation accumulated, the speed limit is executed by this parameter.

If the servo is turned ON with the position deviation accumulated, the speed limit is executed by this parameter. When the command pulse is input in this state, the alarm Er.D02 (Excessive position deviation alarm caused by speed limit during servo ON) is displayed when the set value of Pn264 (maximum position deviation threshold) is exceeded. Pn272 Position deviation clear mode 0x00~0x03 0 - 0x0272 After restart Set the clear mode of the switch position deviation clear signal (/CLR): 0- Clear when level is ON. 1- Clear when the rising edge OFF->ON. 2- Clear when level is OFF. 3- Clear when the falling edge ON->OFF. 4- Position deviation removal .

5- Clear in case of servo off, alarm and limit . Pn273 Selection of position deviation clearing method 0x00~0x02 0 - 0x0273 After restart Set the deviation clearing method: 0- Clear when servo OFF or alarm. 1- Clear when there is /CLR signal. 2- Clear when there is alarm. 3- Do not clear. 4- Clear when servo OFF, alarm, position limit. Note: 1. For details on the pulse amplitude of the clear signal, refer to the description of “Deviation clearance”. 2. In the position control, the position deviation remains unchanged when the servo motor stops due to the travel limit.

Pn274 Positioning completion signal output time 0x00~0x02 0 - 0x0274 After restart Set the output timing of positioning completion signal /COIN: 0- Output when the absolute value of position deviation is less than the positioning completion range (Pn262). 1- Output when the absolute value of position deviation is less than the positioning completion range (Pn262) and the filtered position command is 0. 2- Output when the absolute value of position deviation is less than the positioning completion range (Pn262) and the position command input is 0.