For example, as shown below, after changing the overload warning value (Pn015) from 20% to 50%, the overload warning detection time is half (50%) of the overload alarm detection time. Overload detection time % 100% 200% 2. Change of the detection time of the overload warning (Er. 720) The overload (continuous maximum) alarm (Er. 720) can be detected in advance to prevent motor overload. By detecting the overload alarm by using the “decreased base current”, the overload alarm detection time can be shortened. The detection value of the overload (instantaneous maximum) alarm (Er. 710) cannot be changed.
Motor base current after rating reduction = motor current threshold for calculating overload alarm (default is 1.15 times motor) * motor overload detection base current decrease rated (Pn016). For example, as shown in the following figure, after setting Pn016 to 50%, the overload alarm can be detected earlier because the motor overload is calculated from 50% of the base current. When the value of Pn016 is changed, the overload alarm detection time will be changed.
Overload detection time 100% 200% 78 SD700 Series Servo Technical Manual 50% overload warning detected Overload alarm detection curve 20% overload warning detected Torque 50% overload warning detected 20% overload warning detected 50% overload alarm detection curve 100% overload alarm detection curve Torque command%