Deviation clear signal wiring can be divided into linear driver output and open collector output. Please refer to “Position Command Input Circuit” for wiring details. 1. Clear signal wiring 2. Setting the deviation clear mode The shape of the clear signal is set by Pn272. When Pn272 = 0 or 2, in order to perform clear signal processing, the amplitude of the clear signal must be 250μs or more. When Pn272 = 1 or 3, in order to perform clear signal processing, the amplitude of the clear signal must be 20μs or more. ! Cautions If the setting is set to hold clear, the servo lock function is invalid. As a result, the servo motor will rotate slightly due to drift pulses in the speed loop. 3.

Deviation clearing method selection Depending on the status of the servo unit, you can choose when to clear the position deviation. Set the deviation clearing method by Pn273: 85 SD700 Series Servo Technical Manual Function Parameter Range Default unit Communication When code address enabled Pn272 Position deviation clear mode 0x00~ 0x03 0 - 0x0272 Power down effective Set the clear mode of the digital position deviation clear signal (/CLR): 0-level clear when cleared. 1-rising edge OFF->ON clear. 2-Clear when 2-level OFF. 3-falling edge clears when ON->OFF.

Function Parameter Range Default Unit Communication When enabled code address Pn273 Position deviation clear mode 0x00 ~ 0x02 0 - 0x0273 Power down effective Set themode of the deviation clearing: 0-Servo OFF, alarm, / CLR signal position deviation can be cleared. 1-/CLR signal position deviation can be cleared. 2-Alarm/CLR signal position deviation can be cleared. 3-Cleared in case of servo OFF, alarm and limit. 4-Not clearting the position deviation.