SPRUT — ANALYSIS AND DESIGN OF FLAT SLABS USING VARIOUS CODES

Determine area of punching shear reinforcement per perimeter from: Asw = (vEd 0.75vRd,c)sr u1/(1.5 fywd,ef) Where sr is the radial spacing of shear reinforcement fywd,ef = 250 + 0.25 deff fywd Determine the length of the outer perimeter where shear reinforcement not required from: uout,ef = b VEd/(vRd,c d) Check spacing of bars Min area or reinforcement 1. The minimum area of longitudinal reinforcement in the main direction is As,min = 0.26 fctm bt d/fyk but not less than 0.0013b d. 2. The minimum area of a link leg for vertical punching shear reinforcement is1.5Asw,min /(sr.st) ≥ 0.08 fckЅfyk.

which can be rearranged asAsw,min ≥ ( sr.st)/F where sr = the spacing of the links in the radial direction st = the spacing of the links in the tangential direction F can be obtained from Table 10 Max area of reinforcement Outside lap locations, the maximum area of tension or compress reinforcement should not exceed As,max = 0.4 Ac Minimum spacing of reinforcement The minimum spacing of bars should be the greater of: Bar diameter Aggregate size plus 5 mm 20 mm Max spacing of main reinforcement For slabs less than 200 mm thick the following maximum spacing rules apply: 1. for the principal reinforcement 3h but not more than 400 mm 2. for the secondary reinforcement:

3.5h but not more than 450 mm The exception is in areas with concentrated loads or areas of maximum moment where the following applies: 1. for the principal reinforcement 2h but not more than 250 mm 2. for the secondary reinforcement 3h but not more than 400 mm Where h is the depth of the slab. 35