PLC API Inputs VAR_INPUT fIn : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; bHold : BOOL; END_VAR VAR_OUTPUT fOut : FLOAT; bSampleRateChanged : BOOL; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR Outputs Inputs/ outputs VAR_IN_OUT stParams : ST_CTRL_TuTg_PARAMS; END_VAR stParams consists of the following elements: TYPE ST_CTRL_TuTg_PARAMS : STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fKp : FLOAT := 0; tTu : TIME := T#0ms; tTg : TIME := T#0ms; END_STRUCT END_TYPE TF4100 115 Version:
2.2.4 Name Type Description fIn FLOAT Input value of the TuTg element fManSyncValue FLOAT Input value to which the TuTg element can be set, or that is issued at the output in manual mode. bSync BOOL A rising edge at this input sets the TuTg element to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block. bHold FLOAT A TRUE at this input will hold the internal state (and therefore also the output) constant at its current value, independently of the input value.
Name Type Description fOut FLOAT Output of the TuTg element bSampleRate Changed BOOL Output that indicates whether the function block has internally reduced the sampling rate because of the array being used to delay the input signal not otherwise providing sufficient room. eState E CTRL STATE _ _ State of the function block eErrorId E CTRL _ _ ERRORCODES Supplies the error number [} 173] when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs. Name Type Description stParams ST CTRL TuTg _ _ _ PARAMS Parameter structure of the TuTg element