beckhoff — 12.5.3 AX2xxx Drive - Status and Error Codes

Appendix | Appendix E: AX2xxx parameters TwinCAT 2 460 Version: 1.7 Variable Data Type Value AX2xxx Display Designation is set if offsets of drive current values are too high during startup. 0x00020000 F18 Ballast transistor error with bad ballast transistor respectively preselection of "external ballast resistor" in combination with connected internal ballast resistor, this error is going to be set. 0x00040000 F19 Error missing phase. at PMODE=2. 0x00080000 F20 Slot Error This error condition is generated if there are problems with present slot expansion card (e.g. AX2xxx-B200). This error message is depending on the used expansion slot card type.

It usually points to a faulty interface hardware. 0x00100000 F21 PROFIBUS Handling Error This error can only happen in combination with the use of a Profibus expansion card (part no.: AX2xxx-B310). 0x00200000 F22 Drive circuits are grounded to earth potential (PE) 0x00400000 F23 Error in CAN communication This error message BUSOFF is generated directly by level 2 of the internal CAN controller. 0x00800000 F24 Error Watchdog This error is displayed, if the telegram update time exceeded the value set in EXTWD.