TwinCAT PLC Library Hydraulics - Version 1.4 — 5.2 Global constants (from V3.0)

Knowledge Base PLC Library Hydraulics 237 Version: 1.4 Constant Hexadeci- mal Decimal Description dwTcHydAdsErrNoError 0 0 No error. dwTcHydAdsErrUnknownPo rt 16#0006 6 ADS port unknown. Possible causes: • AMS NetID / ADS port address the wrong runtime system or the wrong computer • another project is running in the addressed PLC • the application does not call a MC AxAdsCommServer BkPlcMc [} 198]() _ _ function block dwTcHydAdsErrUnknownTa rget 16#0007 7 Target machine unknown. Possible causes:

• AMS NetID / ADS port address the wrong runtime system or the wrong computer • the target system has not been started • TwinCAT has not been started • the connection is electrically / mechanically interrupted • for communication via Ethernet: the TCP/IP connection is not working dwTcHydAdsErrInvalidIdxGr oup 16#0702 1794 Invalid IndexGroup. Possible causes: • AMS NetID / ADS port address the wrong runtime system or the wrong computer • another project is running in the addressed PLC • application software error (incorrect combination of ADS port / IdxGroup / IdxOffset) dwTcHydAdsErrInvalidIdxOf fset 16#0703 1795 Invalid IndexOffset. Possible causes:

• AMS NetID / ADS port address the wrong runtime system or the wrong computer • another project is running in the addressed PLC • application software error (incorrect combination of ADS port / IdxGroup / IdxOffset) • attempted access to an array element with invalid index (out of bounds) dwTcHydAdsErrRdWrNotPe rmitted 16#0704 1796 Access (write, read) not permitted. Possible causes: • a write access to a variable without write permission was requested dwTcHydAdsErrInvalidSize 16#0705 1797 Size (number of bytes) not permitted. Possible causes: • application software error (incorrect combination of ADS port / IdxGroup / IdxOffset) dwTcHydAdsErrIllegalValue 16#0706 1798 Value not permitted.

Possible causes: • the transferred value is outside absolute parameter limits • the transferred value is outside parameter limits, which have been specified by other already applicable parameters dwTcHydAdsErrNotReady 16#0707 1799 Not ready for operation. Possible causes: • an MC Power BkPlcMc function block was _ _ prompted by its Enable input to activate an axis that is not ready for operation