Knowledge Base PLC Library Hydraulics 240 Version: 1.4 Constant Hexadeci- mal Decimal Description dwTcHydErrCdPosFdEna 16#4358 17240 Movement in the direction of increasing positions without positive direction advance enable is not permitted. dwTcHydErrCdSetVelo 16#4359 17241 The required velocity is not acceptable. dwTcHydErrCdPehTimeout 16#435C 17244 The axis does not reach the target window within the specified time. dwTcHydErrCdNotMoving 16#435D 17245 The axis is not moving, or not in the correct direction. dwTcHydErrCdConsequenti al 16#43A0 17312 Consequential error: The axis was put in an error state due to a problem with another axis.

dwTcHydErrCdEncType 16#4401 17409 The parameter type is invalid. dwTcHydErrCdEncScaling 16#4406 17414 The increment scaling is not permitted. dwTcHydErrCdEncSyncDist 16#4414 17428 The distance between Latch Enable and the sync _ pulse is too small. dwTcHydErrCdEncSetActP os 16#4422 17442 A problem occurred during actual value setting. dwTcHydErrCdPtrPlcEncIn 16#4442 17474 The axis does not have a pointer to an encoder input interface dwTcHydErrCdPtrPlcEncOu t 16#4443 17475 The axis does not have a pointer to an encoder output interface. dwTcHydErrCdEncUnderru n 16#4450 17488 Reported by some encoder types: The actual position has passed the lower count limit of the encoder.

dwTcHydErrCdEncOverrun 16#4451 17489 Reported by some encoder types: The actual position has passed the upper count limit of the encoder. dwTcHydErrCdEncHdwFail ed 16#4464 17508 Drive actuator or encoder report a hardware fault. dwTcHydErrCdSsi 16#4470 17520 An error was detected when operating an SSI encoder. dwTcHydErrCdPosLag 16#4550 17744 The lag error exceeds an active limit. dwTcHydErrCdDriveType 16#4601 17921 The value set in nDrive Type is not permitted. _ dwTcHydErrCdRefVelo 16#4605 17925 Reference velocity (fRefVelo in ST TcHydAxParam) _ is invalid. dwTcHydErrCdStepperStall ed 16#4636 17974 A stall situation was detected.

dwTcHydErrCdPtrPlcDriveIn 16#4642 17986 The axis does not have a pointer to a drive input interface. dwTcHydErrCdPtrPlcDriveO ut 16#4643 17987 The axis does not have a pointer to a drive output interface. dwTcHydErrCdDriveNotRea dy 16#4650 18000 Power section not ready for operation. dwTcHydErrCdTblEntryCou nt 16#4A02 18946 The number of table entries (rows) is not permitted. dwTcHydErrCdTblInvalidMa sterStep 16#4A04 18948 The table contains entries with invalid master step size. dwTcHydErrCdTblNoInit 16#4A10 18960 The table is not initialized. dwTcHydErrCdTblIllegalInd ex 16#4A13 18963 Table index not permitted.

dwTcHydErrCdTblLineCoun t 16#4A15 18965 The number of table entries is too large. dwTcHydErrCdNotStartable 16#4B01 19201 Axis in a state that does not allow it to start. dwTcHydErrCdFuncTimeout 16#4B07 19207 The function was not reported as complete within the specified time. dwTcHydErrCdNotReady 16#4B09 19209 The axis is not in an operable state.