Beckhoff Automation GmbH & Co. KG TX1200 — 7.5 Compiler Errors

Reference programming TX1200 245 Version: 1.3 Number Error Message Possible Cause 4337 Identifier for input expected Insert a valid expression or identifier in the input box. 4338 Box '%s' has no inputs To none of the inputs of the operator POU ' ' a valid expression is assigned. 4339 Typemismatch at output: Cannot convert ' ' to ' '. The type of the expression in the output box is not compatible to that of the expression which should be assigned to it. 4340 Jump requires 'BOOL' as input type Make sure that the input for the jump is a boolean expression. 4341 Return requires 'BOOL' as input type Make sure that the input for the RETURN instruction is a boolean expression.

4342 Expression expected at input 'EN' of the box ' ' Assign a valid boolean expression to the EN input of the box. 4343 Values of Constants: ‘ ’ Input ' ' of box ' ' is declared as VAR INPUT CONSTANT. But to this POU box _ an expression has been assigned in the dialog 'Edit Parameters' which is not type compatible. 4344 'S' and 'R' require 'BOOL' operand Insert a valid boolean expression after the Set resp. Reset instruction. 4345 Invalid Type for parameter ' ' of ' ': Cannot convert ' ' to ' '. An expression is assigned to input ' ' of POU box ' ' which is not type compatible.

4346 Not allowed to use a constant as an output" You can only assign an output to a variable or a direct address with write access. 4347 'VAR IN OUT' parameter needs variable with _ _ write access as input. To VAR IN OUT parameters only variables _ _ with write access can be handed over, because these can be modified within the POU. 4348 Invalid program name ' '. A variable with the same name exists already. You have inserted a program box in the CFC editor, which has the same name as a (global) variable already existing in your project. You must rename accordingly. 4349 Input or output in POU has been deleted: Check all connections to the box.

This errormessage disappears only after the CFC was edited Correct the POU appropriately. 4350 An SFC-Action can not be accessed from outside! SFC actions only can be called within the SFC POU in which they are defined. 4351 Step name is no identifier: ' ' Rename the step or choose a valid identifier as step name. 4352 Extra characters following valid step name:' ' Remove the not valid characters in the step name. 4353 Step name duplicated: ' ' Rename one of the steps. 4354 Jump to undefined Step: ' ' Choose an existent step name as aim of the jump resp. insert a step with name ‚ ’.

4355 A transition must not have any side effects (Assignments, FB-Calls etc.) A transition must be a boolean expression. 4356 Jump without valid Step Name: ' ' Use a valid identifier as aim (mark) of the jump. 4357 IEC-Library not found Check whether the library iecsfc.lib is inserted in the library manager and whether the library paths defined in ‘Project’ ‘Options’ ‘Paths’are correct. 4358 Action not declared: '%s'. Make sure that in the object organizer the action of the IEC step is inserted below the SFC POU and that in the editor the action name is inserted in the box on the right hand of the qualifier.