PMAC Product Guide Example: If a 5000 line/inch (20,000 cts/in) linear encoder is used for position feedback, and a 500 line/rev (2000 cts/rev) rotary encoder is used for velocity loop feedback, and there is a 5-pitch screw, the effective resolution of the velocity encoder is 10,000 cts/in (2000x5), half of the position sensor resolution, so Ix09 should be set to twice Ix08. If the value computed this way for Ix09 does not come to an integer, use the nearest integer value. Motor Safety I-Variables Ix11 Motor x Fatal (Shutdown) Following Error Limit Range: 0 .. 8,388,607 Default: 32000 (2000 counts) Units:

1/16 Count This parameter sets the magnitude of the following error for motor x at which operation will shut down. When the magnitude of the following error exceeds Ix11, motor x is disabled (killed). If the motor’s coordinate system is executing a program at the time, the program is aborted. It is optional whether other PMAC motors are disabled when this motor exceeds its following error limit; bits 21 and 22 of Ix25 control what happens to the other motor (the default is that all PMAC motors are disabled). A status bit for the motor, and one for the coordinate system (if the motor is in one) are set.

If this coordinate system is hardware-selected on JPAN (with I2=0), or software-addressed by the host (with I2=1), the ERLD/ output on JPAN, and the EROR input to the interrupt controller (except for PMAC- VME) are triggered. Setting Ix11 to zero disables the fatal following error limit for the motor. This may be desirable during initial development work, but not in an actual application. A fatal following error limit is an important protection against various types of faults, such as loss of feedback that cannot be detected directly and that can cause severe damage to people and equipment. Note: The units of Ix11 are 1/16 of a count.

Therefore, this parameter must hold a value 16 times larger than the number of counts at which the limit will occur. For example, if the limit is to be 1000 counts, Ix11 should be set to 16,000. Ix12 Motor x Warning Following Error Limit Range: 0 .. 8,388,607 Default: 16000 (1000 counts) Units: 1/16 Counts This parameter sets the magnitude of the following error for motor x at which a warning flag goes true. If this limit is exceeded, status bits are set for the motor and the motor’s coordinate system (if any). The coordinate system status bit is the logical OR of the status bits of all the motors in the coordinate system.

Setting this parameter to zero disables the warning following error limit function. If this parameter is set greater than the fatal following error limit (Ix11), the warning status bit will never go true because the fatal limit will disable the motor first. If bit 17 of Ix03 is set to 1, the motor can be triggered for homing search moves, jog-until-trigger moves, and motion program move-until-trigger moves when the following error exceeds Ix12. This is known as torque-mode triggering because the trigger will occur at a torque level corresponding to the Ix12 limit. 108 I-Variables