omron — Ix19 Motor x Maximum Permitted Motor Jog/Home Acceleration

PMAC Product Guide Warning: Do not set both the TA and TS times to zero, or a division-by-zero error will occur in the move calculations, possibly causing erratic movement. It is possible to have this limit govern the acceleration for all LINEAR-mode moves by setting very low TA and TS times. The minimum acceleration time settings that should be used are TA1 with TS0. When moves are broken into small pieces and blended together, this limit can affect the velocity, because it limits the calculated deceleration for each piece, even if that deceleration is never executed, because it blends into the next piece. This limit does not affect PVT , CIRCLE , RAPID , or SPLINE moves.

The calculation does not take into account any feedrate override (%value other than 100). If PMAC’s circular interpolation function is used at all, then I13 must be greater than zero, and Ix17 will not be active as an acceleration limit. Example: Given axis definitions of #1->10000X , #2->10000Y , an Ix17 for each motor of 0.25 and the following motion program segment: INC F10 TA200 TS0 X20 Y20 the rate of acceleration from the program at the corner for motor #2 (X) is ((0-10)units/sec * 10000 cts/unit * sec/1000msec) / 200 msec = -0.5 cts/msec 2 . The acceleration of motor #2 (Y) is +0.5 cts/msec 2 . Since this is twice the limit, the acceleration will be slowed so that it takes 400 msec.

With the same setup parameters, and the following program segment: INC F10 TA200 TS0 X20 Y20 X-20 Y20 the rate of acceleration from the program at the corner for motor #1 (X) is ((-7.07-7.07)units/sec * 10000 cts/unit * sec/1000msec) / 200 msec = -0.707 cts/msec 2 . The acceleration of motor #2 (Y) is 0.0. Since motor #1 exceeds its limit the acceleration time will be lengthened to 200 * 0.707/0.25 = 707 msec. Note that in the second case, the acceleration time is made longer (the corner is made larger) for what is an identically shaped corner (90 o ). In a contouring XY application, this parameter should not be relied upon to produce consistently sized corners.

Ix19 Motor x Maximum Permitted Motor Jog/Home Acceleration Range: Positive floating point Default: 0.015625 Units: counts/msec 2 This parameter sets a limit to the commanded acceleration magnitude for jog and home moves, and for RAPID -mode programmed moves of motor x. If the acceleration times in force at the time (Ix20 and Ix21) request a higher rate of acceleration, this rate of acceleration will be used instead. The calculation does not take into account any feedrate override (%value other than 100). Warning: Do not set both Ix20 and Ix21 to 0, or a division-by-zero error will result in the move calculations, possibly causing erratic operations. I-Variables 111