omron — Ix21 Motor x Jog/Home S-Curve Time

PMAC Product Guide Since jogging movesare not coordinated between motors, mostprefer to specify jog acceleration by rate, not time. To do this, simply set Ix20 and Ix21 low enough that the Ix19 limit is always used. The minimum acceleration time settings that should be used are Ix20=1 and Ix21=0. The default limit of 0.015625 counts/msec 2 is quite low and probably will limit acceleration to a lower value than is desired in most systems; most will eventually raise this limit. This low default was used for safety reasons. Example:

With Ix20 (accel time) at 100 msec, Ix21 (S-curve time) at 0, and Ix22 (jog speed) at 50 counts/msec, a jog command from stop would request an acceleration of (50 cts/msec) / 100 msec, or 0.5 cts/msec 2 . If Ix19 were set to 0.25, the acceleration would be done in 200 msec, not 100 msec. With the same parameters in force, an on-the-fly reversal from positive to negative jog would request an acceleration of (50-(-50) cts/msec) / 100 msec, or 1.0 cts/msec 2 . The limit would extend this acceleration period by a factor of 4, to 400 msec. Motor Movement I-Variables Ix20 Motor x Jog/Home Acceleration Time Range: 0 .. 8,388,607 Default: 0 (so Ix21 controls) Units:

msec This parameter establishes the time spent in acceleration in a jogging, homing, or programmed RAPID - mode move (starting, stopping, and changing speeds). However, if Ix21 (jog/home S-curve time) is greater than half this parameter, the total time spent in acceleration will be two times Ix21. Therefore, if Ix20 is set to 0, Ix21 alone controls the acceleration time in pure S-curve form. In addition, if the maximum acceleration rate set by these times exceeds what is permitted for the motor (Ix19), the time will be increased so that Ix19 is not exceeded. Warning:

Do not set both Ix20 and Ix21 to 0 simultaneously, even if relying on Ix19 to limit the acceleration or a division-by-zero error will occur in the jog move calculations, possibly resulting in erratic motion. A change in this parameter will not take effect until the next move command. For instance, for a different deceleration time in a jog move, specify the acceleration time, command the jog, change the deceleration time, then command the jog move again (e.g. J= ), or at least the end of the jog ( J/ ). Ix21 Motor x Jog/Home S-Curve Time Range: 0 .. 8,388,607 Default: 50 Units:

msec This parameter establishes the time spent in each half of the S for S-curve acceleration in a jogging, homing, or RAPID -mode move (starting, stopping, and changing speeds). If this parameter is more than half of Ix20, the total acceleration time will be two times Ix21, and the acceleration time will be pure S- curve (no constant acceleration portion). If the maximum acceleration rate set by Ix20 and Ix21 exceeds what is permitted for the motor (Ix19), the time will be increased so that Ix19 is not exceeded. 112 I-Variables