omron — Application Presets: A1-06

4.5 Application Presets Always disabled for single phase drives. Table 4.18 Parameters Automatically Saved as Preferred (A2-01 to A2-16) Note: A sequence to release the brake is needed when the multi-function output photocoupler P2-PC closes. Hoist Application Preset Specifics on page 115 for more information. 114 OYMC TOEP C71060622-01-OY V1000 User Manual No. Parameter Name Optimum Setting C1-01 Acceleration Time 1 3.0 s C1-02 Deceleration Time 1 3.0 s C6-01 Duty Cycle 0: Heavy Duty C6-02 Carrier Frequency Selection 2: 5 kHz d1-01 Frequency Reference 1 6.0 Hz d1-02 Frequency Reference 2 30.0 Hz d1-03 Frequency Reference 3 50.0 Hz H1-05 Multi-Function Digital Input Terminal S5 Function 3:

Multi-Step Speed 1 H1-06 Multi-Function Digital Input Terminal S6 Function 4: Multi-Step Speed 2 H2-02 Terminals P1 Function Selection (open-collector) 37: During frequency output L3-04 Stall Prevention Selection during Decel 0: Disabled L8-05 Input Phase Loss Protection Selection 1: Enabled L8-07 Output Phase Loss Protection 1: Triggered when a single phase is lost L8-38 Carrier Frequency Reduction 1: Always derated L8-41 Current Alarm Selection 1: Enabled (alarm output) No. Parameter Name No.

Parameter Name b1-01 Frequency Reference Selection d1-03 Frequency Reference 3 C1-01 Acceleration Time 1 E2-01 Motor Rated Current C1-02 Deceleration Time 1 H1-05 Multi-Function Digital Input Terminal S5 Function C6-02 Carrier Frequency Selection H1-06 Multi-Function Digital Input Terminal S6 Function d1-01 Frequency Reference 1 H2-01 Terminals MA, MB, and MC Function Selection d1-02 Frequency Reference 2 L1-01 Motor Overload Protection Selection