omron — Auto-Tuning

4.7 Test Run ■ Auto-Tuning Selection Figure 4.28 START Select the Motor Control Mode A1-02 V/f Control A1-02 = 0 Open Loop Vector A1-02 = 2 PM Open Loop Vector Control A1-02 = 5 Start-Up Programming & Operation Select a V/f pattern E1-03 Will the application allow motor rotation for Auto-Tuning? Can the load be disconnected from the motor? NO Is the total connected load expected to be less than 30% of the motor rating? 4 YES NO NO YES YES Is the cable between the motor and drive longer than 50 m? NOTICE: Auto-Tuning with a connected load is possible, but may result in less than optimum performance.

V/f Rotational Auto-Tuning (T1-01 = 3) NO YES Stationary Auto-Tuning for Terminal Resistance Only (T1-01 = 2) Rotational Auto-Tuning (T1-01 = 0) Select V/f Control Mode (A1-02 = “0”) for the drive. Note: Manually set parameters when OLV control is needed. Run the motor without the load. Connect the load and run the motor. Verify system operates as required. Auto-Tuning finished. Figure 4.28 OYMC TOEP C71060622-01-OY V1000 User Manual 151