4.7 Test Run ■ Before Auto-Tuning the Drive Check the items below before Auto-Tuning the drive: Basic Auto-Tuning Preparations • Auto-Tuning automatically determines the electrical characteristics of the motor. This is fundamentally different from other types of Auto-Tuning features used in servo systems. • Before auto-tuning, be sure the input supply voltage equals or exceeds the motor rated voltage. Performance can be enhanced by using a motor with a base voltage that is 20 V (40 V for 400 V class models) lower than the input supply voltage. This may be of special importance when operating the motor above 90% of base speed, where high torque precision is required.
• Auto-Tuning is not possible with permanent magnet motors. • To cancel Auto-Tuning, press the STOP key on the LED operator. • The next table describes digital input and output terminal status during Auto-Tuning. WARNING! When non rotarional Auto-Tuning is used in applications that utilize a mechanical brake, take special precaution to insure the brake stays applied. Auto-Tuning activates the drive multi-function outputs per the table above. Therefore, a brake may be released while the motor is uncoupled from the load, resulting in an unsafe condition. Proper precautions must therefore be taken prior to performing Auto- Tuning. Note:
It is recommended that Rotational Auto-Tuning be performed with the load disconnected. Failure to comply could result in improper drive operation. If rotational Auto-Tuning is performed for a motor coupled to a load, the motor constants will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple the motor from the load. Rotational Auto-Tuning for V/f Control • Motor rotates during Auto-Tuning. • Sets parameters required for torque compensation, slip compensation, energy savings, and speed search. • Available only when the drive is set for V/f Control. • Required to perform Estimation-Type Speed Search when using V/f Control.
Rotational Auto-Tuning for Open Loop Vector Control • Used only when in Open Loop Vector Control. • Perform only with the motor uncoupled from the load for applications requiring high performance over a wide speed range. • Disconnect the load before Auto-Tuning the drive and motor. Performing Rotational Auto-Tuning with the load connected will set motor parameters incorrectly, and also be dangerous because irregular motor rotation will occur. • It is possible to perform Rotational Auto-Tuning with a connected load if the load is less than 30% of the rated load. • Ensure a motor-mounted brake is fully released.
152 OYMC TOEP C71060622-01-OY V1000 User Manual Auto-Tuning Type Digital Input Digital Output Auto-Tuning for Energy Savings in V/f Control Not available Works the same during normal operation Rotational-Type Auto-Tuning Not available Works the same during normal operation Auto-Tuning for Resistance between Lines Not available Maintains the status at the start of Auto-Tuning