4.7 Test Run • Connected machinery should not produce enough power to rotate the motor. Stationary Auto-Tuning for Terminal Resistance Only • If the motor cable lead length has been significantly modified after Auto-Tuning has already been performed, perform Stationary Auto-Tuning with the new cables. • Perform when using motor cables longer than 50 m with V/f Control. WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning for line-to-line resistance only, the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury from electrical shock. Note:

When auto-tuning a motor that is used on an application in conjunction with a brake, take special precaution to ensure the brake stays applied. Start-Up Programming & Operation ■ Auto-Tuning Fault Codes Calculation of abnormal measurements or pressing before completion will interrupt Auto-Tuning. STOP Refer to Auto-Tuning Errors on page 182 for more information. Figure 4.29 A B 4 A – Normal Auto-Tuning Display B – Auto-Tuning Interrupted Figure 4.29 Auto-Tuning Interruption Display ■ Performing Auto-Tuning The following example illustrates how to perform Rotational Auto-Tuning. Note: The following example is shown with the drive in Open Loop Vector Control (A1-02 = 2).

Selecting the Type of Auto-Tuning OYMC TOEP C71060622-01-OY V1000 User Manual 153 Step D isplay/Result 1. Turn on the power to the drive. The initial display appears. ⇒ 2. Press the key until the Auto-Tuning screen appears. ⇒ 3. Press to begin setting parameters. ⇒