4.7 Test Run To begin rotating the motor: ◆ Multi-Step Speed Operation (4-Step Speed) Select up to 17 preset references (including Jog reference) using five multi-function inputs S3 through S6. Four multi-step references can be selected using two multi-function inputs as illustrated in. ■ Multi-Step Speed Operation Parameters ■ Digital Input 164 OYMC TOEP C71060622-01-OY V1000 User Manual Step Display/Result Turn the power on to the drive. The initial display appears.Note: Set 1. the drive to REMOTE. ⇒ With multi-function contact input terminal S6 closed, the motor 2. rotates forwards at 6 Hz. Note: No run command is necessary when using the Jog frequency. ⇒ Motor 3.
The drive will stop with terminal S6 open. ⇒ No. Name Description d1-01 Frequency Reference 1 Frequency reference. o1-03 determines the units, with Hz as the default. d1-02 Frequency Reference 2 Frequency reference when multi-function input “Multi-Step Speed Reference 1" (H1- = 3) is on. Setting unit: set by o1-03. d1-03 Frequency Reference 3 Frequency reference when multi-function input “Multi-Step Speed Reference 2” (H1- = 4) is on. Setting unit: set by o1-03. d1-04 Frequency Reference 4 Frequency reference when multi-function input “Multi-Step Speed Reference 1, 2" (H1- = 3 and 4) are both on. Setting unit: set by o1-03.
Terminal Parameter Setting Contents S5 H1-05 3 Multi-Step Speed Reference 1 S6 H1-06 4 Multi-Step Speed Reference 2