omron — Multi-Step Speed Operation (4-Step Speed)

4.7 Test Run ■ Wiring Example Set up external switches SW1 and SW2. Figure 4.32 M Start-Up Programming & Operation Figure 4.32 Control Terminals for 4 Multi-Step Speeds Figure 4.33 Frequency Reference Freq Ref 4 Freq Ref 2 Freq Ref 3 4 Freq Ref 1 Forward/Reverse Run/Stop Multi-Step Speed 1 OFF Multi-Step Speed 2 OFF ■ Setting Procedure Figure 4.33 4-Step Speed Time Chart OYMC TOEP C71060622-01-OY V1000 User Manual 165 Three-Phase, 200 Vac (AC400 V) SW1 SW2 Drive R/L1 U/T1 S/L2 V/T2 T/L3 W/T3 S5 S6 SC ON ON ON O N Step Display/Result 1. Turn on the power to the drive. The initial display appears. ⇒ Set the frequencies listed below to the specified parameters: 1. d1-01 = 5 Hz: Step 1 2. 2.

d1-02 = 20 Hz: Step 2 3. d1-03 = 40 Hz: Step 3 4. d1-04 = 50 Hz: Step 4 3. Press the key until the initial display appears. 4. turns on. ⇒