omron — Multi-Step Speed Operation (4-Step Speed)

4.7 Test Run Note: 1. When the drive is in LOCAL mode or if the drive in REMOTE mode and the frequency reference source is set to operator keypad (b1-01/15 = 0), the value in d1-01 is used as frequency reference if speed step 1 is selected. 2. When the drive is in REMOTE mode and the frequency reference source is set to analog input (b1-01/ 15 = 1), the analog input A1 value becomes the frequency reference when speed step 1 is selected. 3. If the function “Auxiliary Frequence” is assigned to an analog input A2 (H3-10 = 2), the terminal A2 input value becomes the frequency reference when speed step 2 is selected. 166 OYMC TOEP C71060622-01-OY V1000 User Manual Step Display/Result 5.

Press to select LOCAL. The LO/RE light will turn on. ⇒ STOP Off On 6. Press RUN to run the motor at 5 Hz. The RUN light will turn on. ⇒ STOP Off On With SW1closed, the drive runs the motor at Multi-Step Speed 2 7. (20 Hz). With SW1 open and SW2 closed, the drive runs the motor at 8. Multi-Step 3 (40 Hz). ⇒ ⇒ With both SW1 and SW2 closed, the drive runs the motor at 9. Multi-Step 4 (50 Hz). 10. Press STOP to stop the drive. The RUN light will flash until the motor comes to a complete stop. ⇒ ⇒ ST Flashing OP Off