omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 191 The acceleration or deceleration times are too short. • Calculate the torque needed during acceleration relative to the load inertia and the specified acceleration time. • If the right amount of torque cannot be set, make the following changes: • Increase the acceleration time (C1-01, -03, -05, -07) • Increase the S-curve characteristics (C2-01 through C2-04) • Increase the capacity of the drive. The drive is attempting to operate a specialized motor or a motor larger than the maximum size allowed. • Check the motor capacity.

• Ensure that the rated capacity of the drive is greater than or equal to the capacity rating found on the motor nameplate. Magnetic contactor (MC) on the output side of the drive has turned on or off. Set up the operation sequence so that the MC is not tripped while the drive is outputting current. V/f setting is not operating as expected. • Check the ratios between the voltage and frequency. • Set parameter E1-04 through E1-10 appropriately. Set E3-04 through E3-10 when using a second motor. • Lower the voltage if it is too high relative to the frequency. Excessive torque compensation. • Check the amount of torque compensation.

• Reduce the torque compensation gain (C4-01) until there is no speed loss and less current. Drive fails to operate properly due to noise interference. • Review the possible solutions provided for handling noise interference. • Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring. Overexcitation gain is set too high. • Check if fault occurs simultaneously to overexcitation function operation. • Consider motor flux saturation and reduce the value of n3-13 (Overexcitation Deceleration Gain). Run command applied while motor was coasting. • Enable Speed Search at start (b3-01 = “1”).

• Program the Speed Search command input through one of the multi-function contact input terminals (H1- = “61” or “62”). The wrong motor code has been entered for PM Open Loop Vector (Yaskawa motors only). Enter the correct motor code to E5-01 to indicate that a PM motor is connected. The motor control method and motor do not match. • Check which motor control method the drive is set to (A1-02). • For IM motors, set A1-02 = “0” or “2”. • For PM motors, set A1-02 = “5”. The motor cable is too long. Use a larger drive. LED Operator Display Fault Name oFA00 Option Card Fault (Port A) The option card is incompatible with the drive.

Cause Possible Solution The option card is incompatible with the drive. Use a compatible option card. LED Operator Display Fault Name oFA01 Option Card Fault (Port A) Replace the option card.