5.4 Fault Detection 192 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solution The option card is not connected properly to the drive. Turn the power off and reconnect the option card. LED Operator Display Fault Name oFA03 Option Card Fault (port A) Option card self-diagnostic error oFA04 Option Card Fault (port A) An error occurred attempting to write to the option card memory. thru oFA30 thru oFA43 Option Card Fault (port A) Communication ID error Cause Possible Solution Option card or hardware is damaged. Replace the option card. Contact OYMC or an OYMC representative for consultation.
LED Operator Display Fault Name oH Heatsink Overheat The temperature of the heatsink exceeded the value set to L8-02 (90-100°C). Default value for L8-02 is determined by drive capacity (o2-04). Cause Possible Solution Surrounding temperature is too high. • Check the temperature surrounding the drive. Verify temperature is within drive specifications. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat. Load is too heavy. • Measure the output current. • Decrease the load. • Lower the carrier frequency (C6-02). Internal cooling fan is stopped.
• Replace the cooling fan. Refer to Cooling Fan Replacement on page 250. • After replacing the drive, reset the cooling fan maintenance parameter (o4-03 = “0”). LED Operator Display Fault Name oH1 Overheat 1 (Heatsink Overheat) The temperature of the heatsink has exceeded the value set to L8-02 (100-110°C). Default value for L8-02 is determined by drive capacity (o2-04). Cause Possible Solution Surrounding temperature is too hot. • Check the temperature surrounding the drive. • Improve the air circulation within the enclosure panel. • Install a fan or air conditioner to cool the surrounding area. • Remove anything near the drive that might be producing excessive heat. Load is too heavy.
• Measure the output current. • Reduce the load. • Lower the carrier frequency (C6-02).