omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection OYMC TOEP C71060622-01-OY V1000 User Manual 193 The internal cooling fan has reached its performance life or has malfunctioned. • Check the maintenance time for the cooling fan (U4-04). • If U4-04 exceeds 90%, replace the cooling fan. Refer to Cooling Fan Replacement on page 250. • After replacing fan, reset the fan maintenance time (o4-03 = “0”). Current flowing to control circuit terminal +V exceeded the tolerance level. • Check the current level of the terminal. • Set the current to the control circuit terminal to be 20 mA or less.

LED Operator Display Fault Name oH3 Motor Overheat Alarm (PTC Input) • The motor overheat signal to analog input terminal A1 or A2 exceeded the alarm detection level. • Detection requires multi-function analog input H3-02 or H3-10 be set to “E”. Cause Possible Solution Motor has overheated • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve reducing E1-08 and E1-10. • Be careful not to lower E1-08 and E1-10 excessively, as this reduces load tolerance at low speeds. • Check the motor-rated current.

• Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. 5 LED Operator Display Fault Name oH4 Motor Overheat Fault (PTC Input) • The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level. • Detection requires that multi-function analog input H3-02 or H3-10 = “E”. Cause Possible Solution Motor has overheated. • Check the size of the load, the accel/decel times and the cycle times. • Decrease the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Adjust the preset V/f pattern (E1-04 through E1-10).

This will mainly involve reducing E1-08 and E1-10.Be careful not to lower E1-08 and E1-10 excessively because this reduces load tolerance at low speeds • Check the motor-rated current. • Enter the motor-rated current as indicated on the motor nameplate (E2-01). • Ensure the motor cooling system is operating normally. • Repair or replace the motor cooling system. LED Operator Display Fault Name oL1 Motor Overload The electrothermal sensor tripped overload protection.