omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection 194 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solution Load is too heavy. Reduce the load. Cycle times are too short during acceleration and deceleration. Increase the acceleration and deceleration times (C1-01 through C1-08). • Drive overloaded at low speeds. • Overload may occur at low speeds when using a general-purpose motor, even if operating within the rated current limitation. • Reduce the load. • Increase the speed. • If the drive is supposed to operate at low speeds, either increase the motor capacity or use a motor specifically designed to operate with the drive.

Although a special type of motor is being used, the motor protection selection is set for a general-purpose motor (L1-01 = 1). Set L1-01 = “2”. Voltage is too high for the V/f characteristics. • Adjust the user set V/f patterns (E1-04 through E1-10). Parameters E1-08 and E1-10 may need to be reduced. • If E1-08 and E1-10 are set too high, there may be very little load tolerance at low speed. The wrong motor-rated current is set to E2-01. • Check the motor-rated current. • Enter the value written on the motor nameplate to parameter E2-01. The maximum frequency for the drive input power is set too low. • Check the rated frequency indicated on the motor nameplate.

• Enter the rated frequency to E1-06 (Base Frequency). Multiple motors are running off the same drive. Disable the Motor Protection function (L1-01 = “0”) and install a thermal relay to each motor. The electrical thermal protection characteristics and motor overload characteristics do not match. • Check the motor characteristics. • Correct the value set to L1-01 (Motor Protection Function). • Install an external thermal relay. The electrical thermal relay is operating at the wrong level. • Check the current rating listed on the motor nameplate. • Check the value set for the motor-rated current (E2-01). Cause Possible Solution Overexcitation current is enabled.

• Overexcitation is a potential serious danger to the motor. • Reduce the excitation deceleration gain (n3-13). • Set L3-04 (Stall Prevention during Deceleration) to a value other than 4. • Disable overexcitation (n3-23 = “0”). Speed Search related parameters are not set to the proper values. • Check values set to Speed Search related parameters. • Adjust the Speed Search current and Speed Search deceleration times (b3-02 and b3-03 respectively). • After Auto-Tuning, enable Speed Estimation Type Search (b3-24 = “1”). Output current fluctuation due to input phase loss. Check the power supply for phase loss.

LED Operator Display Fault Name oL2 Drive Overload The thermal sensor of the drive triggered overload protection. Cause Possible Solution Load is too heavy. Reduce the load.