omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection 196 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solution Excessive load inertia. • Reduce deceleration times using parameters C1-02, -04, -06 and -08 in applications that do not use High-slip Braking. • Use a braking resistor to shorten deceleration time. Motor is driven by the load. Something on the load side is restricting deceleration. The overload time during High-slip Braking is too short. • Increase parameter n3-04 (High-slip Braking Overload Time). • Install a thermal relay and increase the parameter setting of n3-04 to the maximum value.

LED Operator Display Fault Name oPr Digital Operator Connection Fault • The LCD operator has been disconnected from the drive. Note: An oPr fault will occur when all of the following conditions are true: • Output is interrupted when the operator is disconnected (o2-06 = 1). • The run command is assigned to the LCD operator (b1-02 = 0 and LOCAL has been selected). Cause Possible Solution LCD operator is not properly connected to the drive. • Check the connection between the LCD operator and the drive. • Replace the cable if damaged. • Turn off the drive input power and disconnect the LCD operator. Next reconnect the operator and turn the drive input power back on.

LED Operator Display Fault Name oS Overspeed (Simple V/f with PG) Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting. Cause Possible Solution Overshoot or undershoot is occurring. • Adjust the gain by using the pulse train input parameters (H6-02 through H6-05). • Increase the settings for C5-01 (Speed Control Proportional Gain 1) and reduce C5-02 (Speed Control Integral Time 1). Incorrect PG pulse settings. Set the H6-02 (Pulse Train Input Scaling) = 100%, the number of pulses during maximum motor revolutions. Inappropriate parameter settings. Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).

LED Operator Display Fault Name ov Overvoltage Voltage in the DC bus has exceeded the overvoltage detection level. For 200 V class: approximately 410 V For 400 V class: approximately 820 V (740 V when E1-01 is less than 400) Cause Possible Solution Deceleration time is too short and regenerative energy flows from the motor into the drive. • Increase the deceleration time (C1-02, -04, -06, -08). • Install a braking resistor or a dynamic braking resistor unit. • Enable stall prevention during deceleration (L3-04 = “1”). Stall prevention is enabled as the default setting.