omron — Fault Displays, Causes, and Possible Solutions

5.4 Fault Detection OYMC TOEP C71060622-01-OY V1000 User Manual 197 Acceleration time is too short. • Check if sudden drive acceleration triggers an overvoltage alarm. • Increase the acceleration time. • Use longer S-curve acceleration and deceleration times. Excessive braking load. The braking torque was too high, causing regenerative energy to charge the DC bus. Reduce the braking torque, use a braking option, or lengthen decel time. Surge voltage entering from the drive input power. Install a DC reactor. Note: Voltage surge can result from thyristor convertor and phase advancing capacitor using same drive main input power supply.

Ground fault in the output circuit causing the DC bus capacitor to overcharge. • Check the motor wiring for ground faults. • Correct grounding shorts and turn the power back on. Improper Setting of Speed Search related parameters. (Includes Speed Search after a momentary power loss and after a fault restart.) • Check the settings for Speed Search related parameters. • Enable Speed Search Retry function (b3-19 greater than or equal to 1 to 10). • Adjust the current level during Speed Search and the deceleration time (b3-02 and b3-03 respectively). • Perform Line-to-Line Resistance Auto-Tuning and then enable Speed Estimation Type Speed Search (b3-24 = “1”).

Excessive regeneration when overshoot occurs after acceleration. Enable the Overvoltage Suppression function (L3-11 = “1”). Lengthen the S-curve at acceleration end. Drive input power voltage is too high. • Check the voltage. • Lower drive input power voltage within the limits listed in the specifications. The dynamic braking transistor is damaged. Replace the drive. 5 The braking transistor is wired incorrectly. • Check braking transistor wiring for errors. • Properly rewire the braking resistor device. Drive fails to operate properly due to noise interference. • Review the list of possible solutions provided for controlling noise.

• Review the section on handling noise interference and check the control circuit lines, main circuit lines and ground wiring. Load inertia has been set incorrectly. • Check the load inertia settings when using KEB, overvoltage suppression or Stall Prevention during deceleration. • Adjust L3-25 (Load Inertia Ratio) in accordance with the load. Braking function is being used in PM Open Loop Vector Control. Connect a braking resistor. Motor hunting occurs. • Adjust the parameters that control hunting. • Set the hunting prevention gain (n1-02). • Adjust the AFR time constant (n2-02 and n2-03) when in OLV Control.

• Use parameters n8-45 (PM Speed Feedback Detection Suppression Gain) and n8-47 (Pull-In Current Compensation Time Constant). LED Operator Display Fault Name PF Input Phase Loss Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1 (enabled). Cause Possible Solution There is phase loss in the drive input power. • Check for wiring errors in the main circuit drive input power. • Correct the wiring.