5.4 Fault Detection 198 OYMC TOEP C71060622-01-OY V1000 User Manual There is loose wiring in the drive input power terminals. • Ensure the terminals are tightened properly. • Apply the tightening torque specified in this manual to fasten the terminals. Refer to Wire Gauges and Tightening Torque on page 59 There is excessive fluctuation in the drive input power voltage. • Check the voltage from the drive input power. • Review the possible solutions for stabilizing the drive input power. • Disable Input Phase Loss Detection (L8-05 = “0”). PF is detected if DC bus ripple is too high.
If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. There is poor balance between voltage phases. • Stabilize drive input power or disable phase loss detection. The main circuit capacitors are worn. • Check the maintenance time for the capacitors (U4-05). • Replace the drive if U4-05 is greater than 90%. • Check for anything wrong with the drive input power. • If nothing is wrong with the drive input power, try the following solutions if the alarm continues: • Disable Input Phase Loss Protection selection (L8-05 = “0”). PF is detected if DC bus ripple is too high.
If it is disabled, there is no fault but the ripple is still too high, thereby the capacitors are stressed more and lose lifetime. • Replace the drive. LED Operator Display Fault Name PGo PG Disconnect (for Simple V/f with PG) No PG pulses are received for longer than the time set to F1-14. Cause Possible Solution Pulse input (RP) is disconnected. Reconnect the pulse input (RP). Pulse input (RP) wiring is wrong. Correct the wiring. Motor brake engaged. Ensure the motor brake releases properly. LED Operator Display Fault Name rH Braking Resistor Overheat Braking resistor protection was triggered. Fault detection is enabled when L8-01 = 1 (disabled as a default).
Cause Possible Solution Deceleration time is too short and excessive regenerative energy is flowing back into the drive. • Check the load, deceleration time and speed. • Reduce the load. • Increase the acceleration and deceleration times (C1-01 through C1-08). • Replace the braking option with a larger device that can handle the power that is discharged. Excessive braking inertia. Recalculate braking load and braking power. Then try reducing the braking load and checking the braking resistor settings and improve braking capacity. The proper braking resistor has not been installed. • Check the specifications and conditions for the braking resistor device.
• Select the optimal braking resistor. Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature. Using the braking resistor more frequently than its rating trips the alarm even when the braking resistor surface is not very hot.