5.4 Fault Detection OYMC TOEP C71060622-01-OY V1000 User Manual 201 LED Operator Display Fault Name Uv2 Control Power Supply Voltage Fault Voltage is too low for the control drive input power. Cause Possible Solution L2-02 changed from its default value in drive that is 7.5 kW or smaller without installing a Momentary Power Loss Ride-Thru. Correct parameter L2-02 setting or install optional Momentary Power Loss Ride-Thru unit. The wiring for the control power supply is damaged. • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. Internal circuitry is damaged. • Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur. LED Operator Display Fault Name Uv3 Undervoltage 3 (Inrush Prevention Circuit Fault) The inrush prevention circuit has failed. Cause Possible Solution The contactor on the inrush prevention circuit is damaged. • Cycle power to the drive. Check if the fault reoccurs. • Replace the drive if the fault continues to occur. • Check monitor U4-06 for the performance life of the inrush prevention circuit. • Replace the drive if U4-06 exceeds 90%. 5