5.5 Alarm Detection 5.5 Alarm Detection Alarms are drive protection functions that do not operate the fault contact. The drive will return to original status when the cause of the alarm has been removed. During an alarm condition, the Digital Operator display flashes and an alarm output is generated at the multi-function outputs (H2-01 to H2-03), if programmed. Investigate the cause of the alarm and refer to Table 5.9 for the appropriate action.

◆ Alarm Codes, Causes, and Possible Solutions Table 5.9 Alarm Codes, Causes, and Possible Solutions 202 OYMC TOEP C71060622-01-OY V1000 User Manual LED Operator Display Minor Fault Name bb Baseblock Drive output interrupted as indicated by an external baseblock signal. Cause Possible Solutions Minor Fault (H2- †† = 10) External baseblock signal entered via multi-function input terminal (S1 to S6). Check external sequence and baseblock signal input timing. No output LED Operator Display Minor Fault Name bUS Option Communication Error • After initial communication was established, the connection was lost. • Assign a run command frequency reference to the option card.

Cause Possible Solutions Minor Fault (H2- †† = 10) Connection is broken or master controller stopped communicating. • Check for faulty wiring. • Correct the wiring. • Repair ground wiring or disconnected cables. YES Option card is damaged. If there are no problems with the wiring and the fault continues to occur, replace the option card. YES The option card is not properly connected to the drive. • The connector pins on the option card are not properly lined up with the connector pins on the drive. • Reinstall the option card. YES