omron — Alarm Codes, Causes, and Possible Solutions

5.5 Alarm Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 203 A data error occurred due to noise. • Check options available to minimize the effects of noise. • Take steps to counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Try to reduce noise on the controller side. • Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by OYMC, or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • All wiring for communications devices should be separated from drive input power lines.

Install a noise filter to the input side of the drive input power. YES LED Operator Display Minor Fault Name CALL Serial Communication Transmission Error Communication has not yet been established. Cause Possible Solutions Minor Fault (H2- †† = 10) Communications wiring is faulty, there is a short circuit, or something is not connected properly. • Check for wiring errors. • Correct the wiring. • Remove and ground shorts and reconnect loose wires. YES Programming error on the master side. Check communications at start-up and correct programming errors. YES Communications circuitry is damaged. • Perform a self-diagnostics check. • Replace the drive if the fault continues to occurs.

YES Terminal resistance setting is incorrect. The terminal slave drive must have the internal terminal resistance switch set correctly. Place DIP switch S2 to the ON position. Refer to MEMOBUS/Modbus Switch Settings on page 391. YES LED Operator Display Minor Fault Name CE MEMOBUS/Modbus Communication Error Control data was not received correctly for two seconds. Cause Possible Solutions Minor Fault (H2- †† = 10) A data error occurred due to noise. • Check options available to minimize the effects of noise. • Counteract noise in the control circuit wiring, main circuit lines and ground wiring. • Reduce noise on the controller side.

• Use surge absorbers on magnetic contactors or other equipment causing the disturbance. • Use cables recommended by OYMC or another type of shielded line. The shield should be grounded on the controller side or on the drive input power side. • Separate all wiring for communications devices from drive input power lines. Install a noise filter to the input side of the drive input power. YES