5.5 Alarm Detection 204 OYMC TOEP C71060622-01-OY V1000 User Manual Communication protocol is incompatible. • Check the H5 parameter settings as well as the protocol setting in the controller. • Ensure settings are compatible. YES The CE detection time (H5-09) is set shorter than the time required for a communication cycle to take place. • Check the PLC. • Change the software settings in the PLC. • Set a longer CE detection time (H5-09). YES Incompatible PLC software settings or there is a hardware problem. • Check the PLC. • Remove the cause of the error on the controller side. YES Communications cable is disconnected or damaged. • Check the connector for a signal through the cable.

• Replace the communications cable. YES LED Operator Display Minor Fault Name CrST Can Not Reset Fault reset was being executed when a run command was entered. Cause Possible Solutions Minor Fault (H2- †† = 10) Fault reset was being executed when a run command was entered. • Ensure that a run command cannot be entered from the external terminals or option card during fault reset. • Turn off the run command. YES LED Operator Display Minor Fault Name dEv Speed Deviation (for Simple V/f with PG) According to the pulse input (RP), the speed deviation is greater than the setting in F1-10 for a time longer than the setting in F1-11.

Cause Possible Solutions Minor Fault Output (H2-†† = 10) Load is too heavy Reduce the load. YES Acceleration and deceleration times are set too short. Increase the acceleration and deceleration times (C1-01 through C1-08). YES The load is locked up. Check the machine. YES Parameter settings are inappropriate. Check the settings of parameters F1-10 and F1-11. YES The motor brake engaged. Ensure the brake releases properly. YES