5.5 Alarm Detection 206 OYMC TOEP C71060622-01-OY V1000 User Manual EF5 External fault (input terminal S5) External fault at multi-function input terminal S5. EF6 External fault (input terminal S6) External fault at multi-function input terminal S6. Cause Possible Solutions Minor Fault Output (H2- = 10) An external device has tripped an alarm function. Remove the cause of the external fault and reset the multi-function input value. YES Wiring is incorrect. • Ensure the signal lines have been connected properly to the terminals assigned for external fault detection (H1- = 20 to 2F). • Reconnect the signal line. YES Multi-function contact inputs are set incorrectly.
• Check if the unused terminals have been set for H1- = 20 to 2F (External Fault). • Change the terminal settings. YES LED Operator Display Minor Fault Name FbH Excessive PID Feedback The PID feedback input is higher than the level set in b5-36 for longer than the time set in b5-37, and b5-12 is set to 1 or 4. Cause Possible Solutions Minor Fault Output (H2- = 10) Parameters settings for b5-36 and b5-37 are incorrect. Check parameters b5-36 and b5-37. YES PID feedback wiring is faulty. Correct the wiring. YES Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. YES Feedback input circuit is damaged. Replace the drive.
YES LED Operator Display Minor Fault Name FbL PID Feedback Loss The PID feedback input is lower than the level set in b5-13 for longer than the time set in b5-14, and b5-12 is set to 1 or 4. Cause Possible Solutions Minor Fault Output (H2- = 10) Parameters settings for b5-13 and b5-14 are incorrect. Check parameters b5-13 and b5-14. YES PID feedback wiring is faulty. Correct the wiring. YES Feedback sensor has malfunctioned. Check the sensor and replace it if damaged. YES