5.5 Alarm Detection Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 207 Feedback input circuit is damaged. Replace the drive. YES LED Operator Display Minor Fault Name Hbb Safe Disable Signal Input Both Safe Disable input channels open. Cause Possible Solutions Minor Fault Output (H2- = 10) Both Safe Disable Inputs H1 and H2 are open. • Check if external safety circuit tripped and disabled the drive. • If the Safe Disable function is not utilized, check if the terminals HC, H1 and H2 are linked. YES Internally, both Safe Disable channels are broken. Replace the drive.
YES LED Operator Display Minor Fault Name HbbF Safe Disable Signal Input One Safe Disable input channels open. Cause Possible Solutions Minor Fault Output (H2- = 10) One of the inputs H1 and H2 is open while the other is closed. • Check the wiring to device that controls the Safe Disable inputs. • If the Safe Disable function is not utilized, check if the terminals HC, H1 and H2 are linked properly. YES One of the Safe Disable channels is faulty. Replace the drive. YES LED Operator Display Minor Fault Name HCA Current Alarm Drive current exceeded overcurrent warning level (150% of the rated current). Cause Possible Solutions Minor Fault Output (H2- = 10) Load is too heavy.
• Measure the current flowing through the motor. • Reduce the load or increase the capacity of the drive. YES Acceleration and deceleration times are too short. • Calculate the torque required during acceleration and for the inertia moment. • If the torque level is not right for the load, take the following steps: • Increase the acceleration and deceleration times (C1-01 through C1-08). • Increase the capacity of the drive. YES