5.9 Troubleshooting without Fault Display 5.9 Troubleshooting without Fault Display This section is for troubleshooting problems that do not trip an alarm or fault. ◆ Cannot Change Parameter Settings ◆ Motor Does Not Rotate Properly after Pressing RUN Button or After Entering External Run Command ■ Motor Does Not Rotate 224 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions The drive is running the motor (i.e., the Run command is present). • Stop the drive and switch over to the Programming Mode. • Most parameters cannot be edited during run. The Access Level is set to restrict access to parameter settings.
• Set the Access Level to allow parameters to be edited (A1-02 = 2). The operator is not in the Parameter Setup Mode (the LED screen will display “PAr”). • See what mode the LED parameter is current set for. • Parameters cannot be edited when in the Setup Mode (“STUP”). Switch modes so that “PAr” appears on the screen. A multi-function contact input terminal is set to allow or restrict parameter editing (H1-01 through H1-06 = 1B). • When the terminal is open, parameters cannot be edited. • Turn on the multi-function contact input set to 1B. The wrong password was entered. • If the password entered to A1-04 does not match the password saved to A1-05, then drive settings cannot be changed.
• Reset the password. • If you cannot remember the password: • Display parameter A1-04. Press the STOP button while pressing at the same time. Parameter A1-05 will appear. • Set a new password to parameter A1-05. Undervoltage was detected. • Check the drive input power voltage by looking at the DC bus voltage • (U1-07). • Check all main circuit wiring. Cause Possible Solutions The drive is not in the Drive Mode. • Check if the DRV light on the LED operator is lit. • Enter the Drive Mode to begin operating the motor. Refer to The Drive and Programming Mode on page 93.