5.9 Troubleshooting without Fault Display Troubleshooting 5 OYMC TOEP C71060622-01-OY V1000 User Manual 225 Cause Possible Solutions The LO/RE button was pushed. • Stop the drive and check if the correct frequency reference source is selected. If the operator keypad shall be the source, the LO/RE button LED must be on, if the source is REMOTE, it must be off. • Take the following steps to solve the problem: • Push the LO/RE button. • If o2-01 is set to 0, then the LO/RE button will be disabled. Auto-Tuning has just completed. • When Auto-Tuning has completed, the drive is switched back to the Programming Mode. The Run command will not be accepted unless the drive is in the Drive Mode.
• Use the LED operator to enter the Drive Mode. Refer to The Drive and Programming Mode on page 93. A Fast-Stop was executed and has not yet been reset. Reset the Fast-Stop command. Settings are incorrect for the source that provides the run command. Check parameter b1-02 (Run Command Selection). Set b1-02 so that it corresponds with the correct run command source. 0: LED/LCD operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card One of the Safety Inputs is open. • Check for a short-circuit between terminals H1 and HC. • See if one of the Safety Inputs is open. • Correct any faulty wiring.
There is faulty wiring in the control circuit terminals. • Check the wiring for the control terminal. • Correct wiring mistakes. • Check the input terminal status monitor (U1-10). The drive has been set to accept the frequency reference from the incorrect source. Check parameter b1-01 (Frequency Reference Selection 1). Set b1-01 to the correct source of the frequency reference. 0: LED operator 1: Control circuit terminal (default setting) 2: MEMOBUS/Modbus communications 3: Option card 4: Pulse train input (RP) The terminal set to accept the main speed reference is set to the incorrect voltage and/or current. Check DIP switch S1. Next assign the correct input level to terminal A2 (H3-09).
Refer to Terminal A2 Switch on page 75. Selection for the sink/source mode is incorrect. Check DIP switch S3. Refer to Sinking/Sourcing Mode Switch on page 73. Frequency reference is too low. • Check the frequency reference monitor (U1-01). • Increase the frequency by changing the maximum output frequency (E1-09).