5.9 Troubleshooting without Fault Display ■ Motor Rotates in the Opposite Direction from the Run Command 226 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions Multi-function analog input is set up to accept gain for the frequency reference, but no voltage (current) has been provided. • Check the multi-function analog input settings. • Check if analog input A1 or A2 is set for frequency reference gain (H3-02/10 = 1). If so, check if the correct signal is applied to the terminal. The gain and the frequency reference will be 0 if no signal is applied to the gain input. • Check if H3-02 and H3-10 have been set to the proper values.
• Check if the analog input value has been set properly. The STOP button was pressed when the drive was started from a REMOTE source. • When the STOP button is pressed, the drive will decelerate to stop. • Switch off the run command and then re-enter a run command. • The STOP button is disabled when o2-02 is set to 0. Motor is not producing enough torque in the V/f motor control method. • Ensure the selected V/f pattern corresponds with the characteristics of the motor being used. • Set the correct V/f pattern to E1-03. • When E1-03 = F, increase both the minimum and mid output frequency voltages (E1-08, E1-10).
Increase the frequency reference so that it is higher than the minimum frequency reference (E1-09). Perform Line-to-Line Resistance Auto-Tuning when using particularly long motor cables. Increase the torque compensation gain (C4-01). Motor is not producing enough torque in Open Loop Vector Control. • Execute Rotational Auto-Tuning. • If the motor cables are replaced with longer cables after Rotational Auto-Tuning was performed, Auto-Tuning may need to be repeated due to voltage drop across the line. • Check if the torque limit parameters have been set too low (L7-01 through L7-04). • Reset the torque limit back to its default setting (200%).
Increase both the minimum and mid output frequency voltages (E1-08 and E-10). The drive is set for both 2-wire and 3-wire sequence at the same time. • The drive is set for a 3-wire sequence when one of parameters H1-03 through H1-06 is set to 0. • If the drive is supposed to be set up for a 2-wire sequence, then ensure parameters H1-03 through H1-06 are not set to 0. • If the drive is supposed to be set up for a 3-wire sequence, then H1- must be set to 0. Refer to Table 5.2 for additional information. Cause Possible Solutions Phase wiring between the drive and motor is incorrect. • Check the motor wiring. • Switch two motor cables (U, V, and W) to reverse motor direction.
• Connect drive output terminals U/T1, V/T2 and W/T3 in the right order to the corresponding motor terminals U, V, and W.