omron — Motor Does Not Rotate Properly after Pressing RUN Button or After Entering External Run Command

5.9 Troubleshooting without Fault Display ■ Drive Does Not Allow Selection of Rotational Auto-Tuning ■ Motor Hunting Occurs at Low Speeds ■ Overvoltage Occurs When Running at a Constant Speed 228 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions Insufficient voltage insulation between motor phases. When the motor is connected to terminals U/T1, V/T2, and W/T3, voltage surges occur between the motor coils and drive switching. Normally, surges can reach up to three times the drive input power supply voltage (600 V for 200 V class, and 1200 V for 400 V class). Use a motor with voltage tolerance higher than the max voltage surge.

Use a motor designed to work specifically with a drive when using a 400 V class unit. Install an AC reactor on the output side of the drive. The motor fan has stopped or is clogged. Check the motor fan. Cause Possible Solutions The drive is in the incorrect motor control method for Rotational Auto-Tuning. • Check if the drive is set to V/f Control by accident (A1-02 = 0). • Change the motor control method to Open Loop Vector Control (A1-02 = “2”). Cause Possible Solutions Excessive load inertia in Open Loop Vector Control. • Excess load inertia can cause motor hunting in Open Loop Vector Control due to slow motor response.

• Increase the speed feedback detection control time constant (n2-02) from its default value of 50 ms to an appropriate level between 200 and 1000 ms. Adjust this setting in combination with n2-03 (Feedback Detection Control Time Constant 2). Cause Possible Solutions Excessive load inertia in Open Loop Vector Control. • Loads with a lot of inertia (fans, etc.) can trigger an overvoltage fault when operating in Open Loop Vector Control. • Switch to the V/f motor control method. • Adjust the values set for the speed feedback detection control time constant (n2-02, n2-03).