5.9 Troubleshooting without Fault Display ■ Motor Stalls During Acceleration or With Large Loads ■ Motor Will Not Accelerate or the Acceleration Time is Too Long OYMC TOEP C71060622-01-OY V1000 User Manual 229 Cause Possible Solutions Load is too heavy. • Take the following steps to resolve the problem: • Reduce the load. • Increase the acceleration time. • Increase motor capacity. • Although the drive has a Stall Prevention function and a Torque Compensation Limit function, accelerating too quickly or trying to drive an excessively large load can exceed the capabilities of the motor. Cause Possible Solutions Frequency reference is too low. • Check the maximum output frequency (E1-04).
• Increase E1-04 if it is set too low. Check U1-01 for proper frequency reference. Check if a frequency reference signal switch has been set to one of the multi-function input terminals. Check for low gain level set to terminals A1 or A2 (H3-03, H3-11). Load is too heavy. • Reduce the load so that the output current remains within the motor-rated current. • In extruder and mixer applications, the load will sometimes increase as the temperature drops. 5 Check if the mechanical brake is fully releasing as it should. The torque limit function is operating in Open Loop Vector Control. • Check the torque limit setting. It may be too low. (L7-01 through L7- 04).
• Reset the torque limit to its default value (200%). Acceleration time has been set too long. Check if the acceleration time parameters have been set too long (C1-01, -03, -05, -07). Motor characteristics and drive parameter settings are incompatible with one another in V/f Control. • Select the correct V/f pattern so that it matches the characteristics of the motor being used. • Check E1-03 (V/f Pattern Selection). The right combination of motor characteristics have not been set in Open Loop Vector Control. Execute Rotational Auto-Tuning. Incorrect frequency reference setting. • Check the multi-function analog input settings.
• Check if multi-function analog input terminal A1 or A2 is set for frequency gain (H3-02 or H3-10 = “1”). If so, the frequency reference will be 0 if there is no voltage (current) input provided. • Ensure H3-02 and H3-10 are set to the proper values. • Ensure the analog input value is set to the right value (U1-13, U1-14). The Stall Prevention level during acceleration and deceleration set too low. • Check the Stall Prevention level during acceleration (L3-02). • If L3-02 is set too low, acceleration will take a fair amount of time. • Increase L3-02.