omron — Motor Does Not Rotate Properly after Pressing RUN Button or After Entering External Run Command

5.9 Troubleshooting without Fault Display ■ Drive Frequency Reference Differs from the Controller Frequency Reference Command ■ Poor Speed Control Accuracy 230 OYMC TOEP C71060622-01-OY V1000 User Manual Cause Possible Solutions The Stall Prevention level during run has been set too low. • Check the Stall Prevention level during run (L3-06). • If L3-06 is set too low, speed will drop as the drive outputs torque. • Increase the setting value. Although the drive is operating in Open Loop Vector motor control method, Auto-Tuning has not been performed. • Perform Auto-Tuning. • Calculate motor data and reset motor parameters. • Switch to the V/f motor control method (A1-02 = “0”).

Drive reached the limitations of the V/f motor control method. • The motor cable may be long enough (over 50 m) to require Auto- Tuning for line-to-line resistance. Also be aware that V/f Control is comparatively limited when it comes to producing torque at low speeds. • Consider switching to Open Loop Vector Control. Cause Possible Solutions The analog input frequency gain and bias are set to incorrect values. • Check the frequency reference terminal input gain level assigned to terminals A1 and A2, as well as the frequency reference input bias to terminal A1 and A2 (parameters H3-03, H3-04, and H3-12). • Set these parameters to the appropriate values.

A frequency bias signal is being entered via analog input terminals A1 or A2. • If multi-function analog input terminals A1 and A2 are set for frequency reference (H3-02 = 0 and H3-10 = 0), the addition of both signals builds the frequency reference. • Ensure that H3-02 and H3-10 are set appropriately. • Check the input level set for terminals A1 and A2 (U1-13, U1-14). Cause Possible Solutions Drive reached the slip compensation limit. • Check the slip compensation limit (C3-03). • Increase the value set to C3-03. Motor-rated voltage is set too high in Open Loop Vector Control. • The input voltage for the drive determines the maximum output voltage.

A drive with an input of 200 Vac can only output a maximum of 200 Vac. Open Loop Vector Control sometimes calculates an output voltage reference value that exceeds the maximum drive output voltage level, resulting in a loss of speed control accuracy. • Use a motor with a lower voltage rating (a vector control motor). • Increase the input power voltage. Auto-Tuning did not complete properly for Open Loop Vector Control. • Perform Auto-Tuning again.